UID
10-120kVA
Embedded with isolated transformer, UID three-phase UPS solution raging from 10kva-20kva are designed for harsh environment especially industrial application. With high power factor up to 0.97,full DSP control and online double conversion design, it can offer high levels of reliability and protection for industrial facilities and mission-critical systems, ensuring maximum power reliability.
General Features 

● Online double conversion

● Full DSP control

● High power factor:0.9

● Wide input adaptability:(380Va/400Vac/415Vac) (-25%/+20%)

● Optimized battery management,self-test&lexible battery configuration 

● N+X parallel redundancy

● Strong overload capability:110%/125%/150% overload for 60/10/1min.

● Power walk in

● Generator mode

● LBS synchronization

● Multi-protection

● User-friendly network management


Technical Specification
MODEL EP10-L EP20-L EP30-L EP40-L EP60-L EP80-L  EP100-L EP120-L   EP160-L 
Capacity
 (VA/Watts)
10kVA / 8kW   20kVA / 16kW  30kVA / 24kW 40kVA / 32kW 60kVA /48kW 80kVA/ 64kW 100kVA/ 80kW  120kVA/ 96kW  160kVA/ 128kW  
INPUT    
Operating 
voltage
 range 
380/400/415Vac (-25% / +20% ), (3Ph+N+PE)   
Operating
 frequency 
range
 50/60Hz(±5%)   
Power Factor >0.97 (with filter)   
OUTPUT     
Output Voltage 380/400/415Vac (±1%)   
Output frequency  50/60Hz (±0.05%)   
Harmonic
 Distortion 
(THDv)
<3% with linear load   
Crest factor 3:1 (max)   
Efficiency ≥90.5%  ≥91.5%   
BYPASS   
Rated voltage 380/400/415Vac   
Rated frequency 50/60Hz(auto-sensing)
Voltage
 protection
 range 
Upper limit: +20% (+10%,+15%,+20% adjustable) 
Lower limit: -40% (-10%, -20%, -30%, -40% adjustable)
   
Frequency 
protection
 range
±10% (±2.5%, ±5%,±10%, ±20% adjustable)   
BATTERY   
Battery voltage  384Vdc ( 360~384Vdc )   
SYSTEM FEATURES   
Transfer time 0ms (Line mode →Battery mode)   
Overload ≤110%/60min ,≤125%/10min ,≤150%/1min,to Bypass   
LED display Input, Inverter, Bypass, Battery, Output, Status   
LCD display I/O voltage, frequency, power, power factor, battery voltage, current, battery status,
 load percentage, UPS status, history record
   
Communication
 interface
Dry contact, RS232, RS485, SNMP card (Optional)   
Optional   Harmonic filter, SNMP adapter, LBS cables, battery temperature sensor,Bypass current-sharing inductor   
ENVIRONMENT   
Operating 
Temperature
0℃~40℃   
Storage 
temperature
-25~55℃   
Humidity range 0~95% (non-condensing)   
Altitude  <1500m   
Noise level  <58dB <65dB     
PHYSICAL      
Dimension
 W×D×H (mm)
350×650×1050 430×830×1100   720×675×1400 890×775×1600   
Net weight (kg) 148 163 230 255 386 426 625    685    780 
STANDARDS      
Safety  IEC/EN 62040-1;IEC/EN 60950-1
Performance  IEC 62040-3    
EMC IEC/EN 62040-2;IEC 61000-2-2;IEC 61000-4-2;IEC 61000-4-3;IEC 61000-4-4; IEC 61000-4-5;IEC 61000-4-6;IEC 61000-4-8;IEC 61000-4-11;   