Vanguard II |
![]() |
2000VA, 3000VA |
![]() |
On-line UPS |
Features :
- Double conversion on-line technology with 0.9 power factor
- Input power factor correction (PFC)
- Pure sine wave output with less than 3% T.H.D.
- High efficiency mode selectable
- Free-run mode setting
- Active-fan operation dependant on load level to reduce noise and save energy
- Protections for overload, short circuit, tele-communication, etc.
- Emergency Power Off (EPO) protection
- Remaining backup time display via LED or LCD (optional)
- Extended backup time with battery pack
Specification
MODEL |
VGS-2000 |
VGS-3000 |
|
CAPACITY |
2000VA |
3000VA |
|
1800W |
2700W |
||
INPUT | Voltage |
220V / 230V / 240V |
|
Frequency |
50Hz / 60Hz ±2.5Hz auto sensing (45Hz to 65Hz user selectable) |
||
Phase |
Single phase |
||
Power factor |
> 0.97 |
||
OUTPUT | Voltage |
220V / 230V / 240V ±2% (selectable output voltage) |
|
Frequency |
50Hz / 60Hz ±0.2Hz |
||
Waveform |
Pure sine wave |
||
Phase |
Single phase |
||
Harmonic distortion |
< 5% of T.H.D. at non-linear load |
||
Efficiency |
Approximately 89% |
||
Connections |
*Please refer below "Receptacle Options". Customized receptacle can be discussed. |
||
PROTECTION | Overload protection |
UPS automatic power off if overload exceeds 106% to 120% of nominal at 30 seconds; 121% to 150% for 10 seconds |
|
Short circuit protection |
UPS output cut off immediately or protected by input fuse or circuit breaker |
||
Tele-communication |
RJ45 x2 |
||
Alarm |
Buzzer beeps under backup mode, battery low, battery charging fault, and overload |
||
BATTERY | Type |
Sealed, maintenance-free lead acid battery |
|
Typical recharge time |
4 hours to 90% |
||
Battery quantity |
12V 7Ah x5 |
12V 7Ah x8 |
|
Backup time (100% load) |
3 to 5 minutes |
3 to 4 minutes |
|
Protection |
Battery low cut-off without draining any current |
||
GENERAL | Dimension (W x D x H) |
225mm x 420mm x 358mm |
|
Product weight |
26.5kg(58.3lb) |
31.5kg(69.3lb) |
|
Display (LED/LCD) |
LED - line mode (green), bypass / battery mode (yellow), fault (red) |
||
Communication interface |
Standard - RS-232; *Optional - USB B-type and/or SNMP |
||
Audible noise |
< 50dBA (1m from surface) |
||
Ambient temperature |
+0 °C to +40 °C |
||
Storage temperature |
-15 °C to +50 °C |
||
Humidity |
0-95%, non-condensing |
Communication Interface
Model |
LCD |
CPU |
SNMP |
PFC |
RS-232 |
USB |
VGS-2000 |
|
◆ |
|
◆ |
||
VGS-3000 |
|
◆ |
|
◆ |
||
●Standard Function ○Not Available ◆Optional |