If you do not find the product that you require or the prices are not available ($0) please send us an email/ call us so we can assist. *Sold out products can be made available upon request.
Cart 0
POWERCOM Vanguard II Rack Tower 10KVA

POWERCOM Vanguard II Rack Tower 10KVA

$0.00

Vanguard II Rack Tower
10KVA
On-line UPS

 

Features :

  • Double conversion on-line technology with 0.9 power factor in rack mount design
  • Input power factor correction (PFC)
  • Pure sine wave output with less than 3% T.H.D.
  • High efficiency mode selectable
  • Free-run mode setting
  • Active-fan operation dependant on load level to reduce noise and save energy
  • Protections for overload, short circuit, tele-communication, etc.
  • Emergency Power Off (EPO) protection
  • Remaining backup time display via LED or LCD (optional)
  • Extended backup time with battery pack

  

Specification

 

 

MODEL

VRT-10K

CAPACITY

10000VA / 9000W

INPUT Voltage

 220V / 230V / 240V

120V to 139V under 25% load, 140V to 159V under 50% load, 160V to 179V under 75% load, 180V to 276V with 100% load

Frequency

50Hz / 60Hz ±2.5Hz auto sensing (45Hz to 65Hz user selectable)

Phase

Single phase

Power factor

> 0.97

OUTPUT Voltage

220V / 230V / 240V ±2% (selectable output voltage)

Frequency

50Hz / 60Hz ±0.25Hz

Waveform

Pure sine wave

Phase

Single phase

Harmonic distortion

< 3% of T.H.D. at linear load

Efficiency

Approximately 89%

Connections

*Please refer below "Receptacle Options". Customized receptacle can be discussed.

PROTECTION Overload protection

UPS automatic power off if overload exceeds 106% to 120% of nominal at 30 seconds; 121% to 150% for 10 seconds

Short circuit protection

UPS output cut off immediately or protected by input fuse or circuit breaker

Tele-communication

RJ45 x2

Alarm

Buzzer beeps under backup mode, battery low,  battery charging fault, and overload

BATTERY Type

Sealed, maintenance-free lead acid battery

Typical recharge time

4 hours to 90%

Battery quantity

12V 9Ah x20

Backup time (100% load)

3 to 4 minutes

Protection

Battery low cut-off without draining any current

GENERAL Dimension (W x D x H)

428mm x 690mm x 130mm

Product weight

 93kg(205.03b)

Shipping weight

112kg(246.92lb)

Display (LED/LCD)

LED - line mode (green), bypass / battery mode (yellow), fault (red)

LCD - input / output voltage and frequency, on-line mode, backup mode, battery capacity, load level

Communication interface

Standard - RS-232; *Optional - USB B-type and/or SNMP

Audible noise

< 60dBA (1m from surface)

Ambient temperature

+0 °C to +40 °C

Storage temperature

-20 °C to +50 °C

Humidity

 0-95%,non-condensing

 

Communication Interface
Model
LCD
CPU
SNMP
PFC
RS-232
USB
VRT-10000-RM
Standard Function  Not Available   ◆Optional
Receptacle Options 

 